FIREFLY II PLUS FIRE DOOR RELEASE DEVICE
WITH BATTERY BACKUP


Firefly II Plus Fire Door Release Device with Battery Backup

All-Rite's Firefly II Plus time delay release devices are designed for use on rolling doors, single-slide and center parting level and inclined track doors.  All models are normally energized Fail-Safe Releasing Devices incorporating an internal 72-hour battery pack and state of the art electronic control circuitry. The Firefly II Plus series release devices respond to emergency conditions generated by manual or automatic normally closed initiating devices and shall be used in conjunction with a temperature fuse link system.

Features:

  • Solid state fail safe operation
  • 72-hour battery backup
  • Diagnostic LED's
  • Down limit detection (motor-operated doors)
  • Supports up to 4 Auxiliary Devices
  • Adjustable 0-10 sec. Delay On Alarm Response Release

Applications:

  • For use on all service fire and counter fire doors w/release arm drop out
  • GH, H and GH Operators w/B2 wiring (modification required, see below)

Options:

  • Smoke Detector(s)
  • Sounder Strobe (strobe light & horn)

Operation:
Upon activation of alarm system and/or smoke detector, the unit will initiate delay up to 10 sec before mechanically releasing the unit. In a power outage situation, the battery will power the unit and will not release unless there is an alarm condition or battery becomes discharged. Motor-operated doors may use the down limit detection feature which will prevent release if the door is in the closed position.

Labeling Agency:

  • UL
  • ULC
  • CA State Fire Marshall

Modifications:
Motor operators will require an auxiliary closed limit switch for down limit detection

TECHNICAL SPECIFICATIONS:

Dimensions: 9⅛" high x 9⅛" wide x 4¾" deep

Weight: 13 lbs

Mounting:

Surface only. Unit must be mounted in the vertical or horizontal position near the release arm of the door. Cable or sash pull must be at 90° to the unit.

Electrical Connection:

See Cut Sheets & Wiring (PDF)

Electrical Requirements:

Input
Voltage
Voltage
Requirements
Current Req'd
Supervisory *
Current Req'd
Alarm Condition
120VAC 120VAC ± 10% 0.10A 0.5A
24VAC 24VAC ± 10% 0.10A 0.5A
24VDC 24VDC ± 5% 0.10A 0.5A

* NOTE: Initial power up in rush current not to exceed 3 times rated current

Initiating/Door Inputs (dry contacts):

  • Maximum loop resistance: 100Ω
  • Maximum Current: Not to exceed 0.002A
  • Maximum Voltage: 15 VDC

Auxiliary Inputs:
12VDC @ 0.250A


Battery:
12VDC 4.0 AH